Wire Gauge Calculator

Recommended wire size12 AWG copper
Ampacity used
20 A
Voltage drop
2.65% (3.18 V)
GaugeAmpacityVoltage dropResult
14 AWG15 A4.21%Too small
12 AWG20 A2.65%OK
10 AWG30 A1.66%OK
8 AWG50 A1.05%OK
6 AWG65 A0.66%OK
4 AWG85 A0.41%OK
3 AWG100 A0.33%OK
2 AWG115 A0.26%OK
1 AWG130 A0.21%OK
1/0 AWG150 A0.16%OK
2/0 AWG175 A0.13%OK
3/0 AWG200 A0.1%OK
4/0 AWG230 A0.08%OK

Estimate based on NEC 75 °C ampacities (small conductors limited to 15/20/30 A breakers) and single-phase round-trip voltage drop. Always follow local electrical codes and use a licensed electrician.

Estimate the wire gauge (AWG) needed for a circuit. The calculator checks both the wire’s current rating and the voltage drop over the length of the run.

How to use the Wire Gauge Calculator

  1. Enter the load current in amps.
  2. Enter the one-way length of the wire run and the circuit voltage.
  3. Choose copper or aluminum and the maximum voltage drop (3% is typical).

How it works

Two things limit wire size. Ampacity is how much current a wire can carry without overheating; small conductors are also limited by their breaker (14 AWG copper → 15 A, 12 AWG → 20 A, 10 AWG → 30 A). Voltage drop grows with length: VD = 2 × length × current × resistance per foot. Long runs often need a thicker wire than ampacity alone suggests. The NEC recommends keeping branch-circuit drop to about 3%.

This is a planning estimate. Insulation type, temperature, bundling and local codes all affect the required size — have electrical work checked by a licensed electrician.

Common copper wire sizes

AWGTypical breakerCommon use
1415 ALighting and general outlets
1220 AKitchen, bathroom and garage outlets
1030 AWater heaters, dryers, window AC
840–50 ARanges, large AC units
650–60 AEV chargers, subpanels
470–85 ASubpanels, large feeders

Frequently asked questions

What size wire for a 20 amp circuit?

12 AWG copper for typical runs. For long runs (over about 75–100 ft at 120 V) go up to 10 AWG to limit voltage drop.

What size wire for 30 amps?

10 AWG copper, or 8 AWG aluminum.

What wire size for a 50 amp EV charger?

6 AWG copper is common, depending on insulation type and run length.

Does aluminum wire need to be bigger?

Yes — aluminum has about 64% more resistance than copper, so it is usually one or two sizes larger.